Everlux ULC Listed Egress Path Markings

The Everlux ULC Listed Egress Path Markings include directional exit signs, door hardware markings, no exit signs, floor identification signs and strips for wall and floor applications. This Floor Proximity Egress Path Marking System is in compliance with the requirements of the CAN ULC S572, the UL 1994 Standard for Luminous Egress Path Marking Systems, the Guide for the Installation of Photoluminescent Exit Stairway Markings in Buildings 2008, and the Reference Standards 6-1 and 6-1A (USA) as required by Local Law 26 of 2004, New York City Building Code.

Luminance performance of the Everlux ULC Listed Egress Path Markings:

According to R.S 6.1-A
According to RS 6.1, in stimulation conditions of 21.6 lux (2 ft-c) during 120 minutes with a fluorescent cool white source color temperature 4000K, the ULC listed Everlux Path Marking System sign will deliver the following luminance performance:

Time after removing the exciting light (in minutes)Luminance Intensity (mcd/m2
According to RS 6.1(1)
10 minutes
3049.3
60 minutes
712.3
90 minutes
58.2