Everlux

Everlux offers a comprehensive range of photoluminescent safety signs for a diversified number of applications such as to identify the location of Fire-Fighting Equipment, Fire Alarm Equipment, Emergency Equipment and Escape Route Marking.

This product range is in compliance with NFPA 170 Standard for Fire Safety and Emergency Symbols and meets the requirements of ASTM E2030 Standard Guide for Recommended Uses of Photoluminescent (Phosphorescent) Safety Markings, ASTM E2072 Standard Specification for Photoluminescent (Phosphorescent) Safety Markings and ASTM E2073 Standard Test Method for Photopic Luminance of Photoluminescent (Phosphorescent) Markings.

Luminance performance:

Time after removing the exciting light (in minutes)Luminance Intensity (mcd/m2) 
According to
RS 6.1(1)

According to ASTM-E2073(2)
According to ISO 16069 (3)
10 minutes
30703048140150
60 minutes712----
2021
90 minutes
57.655.5--
--
Decay time
----
--
--
18002000

(1) Stimulation with 4000K fluorescent lamp providing a mean illuminance of 2foot-candles (21.6lux) on the surface of the test specimen for 120 min.
(2) Stimulation with 4000K fluorescent lamp providing a mean illuminance of 1 foot-candle (10.8lux) on the surface of the test specimen for 60 min.
(3) Stimulation with 6500K xenon lamp providing a mean illuminance of 92.9 foot-candle (1000lux) on the surface of the test specimen for 5 min.


To access the complete technical sheet, please go page Technical Datasheets or Downloads